113 Seattle addresses appear in three City and Fire Department records: a Seattle Fire Department elevator rescue call, a code complaint whose text mentions an elevator, and at least one elevator or lift listed by the City as Operating Without Certificate.
Dated City records. These are not findings of fault.
City inspection records from March 2, 2006 and December 16, 2024 both tell the owner to shorten the governor rope on elevator # 734. The records we have do not show whether it was done in between.
In August 1997 the City asked for the leaks to be fixed and the pit of elevator # 734 kept dry. In December 2024 it recorded 8 to 10 inches of water and rusting pit equipment. The same kind of problem came back; this does not show the pit was wet the whole time.
The City's February 26, 2025 inventory lists October 1, 2012 as the last safety test for elevator # 736, more than 12 years earlier, on a five-year cycle. The full test history should be requested before saying a test was missed.
The 2001 letter calls car top wiring on # 734 "a continuous repeat item every year." The 2011 and 2012 letters say many corrections "are repeated from inspection reports of previous years."
Reading the dates: these are the spans between dated City records, not proof that an elevator stayed broken the whole time. A Passed with Conditions result or a Closed complaint does not show that each problem was fixed.
Record numbers open the City's own page for that record
142 Fire Department elevator rescue calls, February 2020 to June 2025. Both elevators (City # 12643 and # 12644) were listed as Operating Without Certificate on January 31, 2026.
One complaint mentioning the elevators was found, filed in November 2024 (013065-24CP): BOTH ELEVATORS ARE OUT DUE TO THE STORM
.
SDCI accepted a safety test for elevator # 12644 on June 29, 2026. A City notice dated August 3, 2026 says certificates were not issued for either elevator; both were still listed as Operating Without Certificate.
The rental registration renewal was issued July 22, 2026 (001-0074751-001R). The City's record list for the address, pulled September 12, 2026, shows three complaints opened before that date still Under Investigation: 004792-23CP, 007493-26CP and 010199-26CP.
16 Fire Department elevator rescue calls, May 2021 to October 2023. 14 complaints mentioning elevators, June 2018 to August 2025.
Two of those complaints, both filed in January 2023, still showed Open Duplicate in the City's data through 2025 (000537-23CP, 000538-23CP). One filed in July 2023 still showed Under Investigation (008525-23CP).
One of the building's three elevators, 2-P (City # 735, EQP-CY-03201), was listed as Operating Without Certificate on January 31, 2026. The other two had active certificates.
The City's elevator inspection letters for this building go back to 1997. See what they asked for, year by year.
This address is not one of the 113. Its one elevator, 1-P (City # 6588, EQP-CY-04902), was listed as Operating Without Certificate on January 31, 2026.
The Fire Department rescue log shows no elevator rescue calls here, and no code record here mentions an elevator, so it does not meet the three-record match. It appears at the bottom of the table for reference.
The City's data through 2025 holds 20 code records for this address; 17 have no last inspection date. A missing date in the open data does not by itself show that no inspection happened.
Lowell / Emerson Apartments · elevators # 734, # 735 and # 736, in service since 1956
The August 1997 and October 1998 inspection letters both say to replace the governor cables on # 735 because of excessive crown and valley breaks.
Elevator or fire service keys are listed as missing from the key box in 1997, 1998, 2001, 2003, 2010, 2011, 2012 and 2013. Firefighters use these keys to run the elevators in an emergency.
Phase II fire service on the Emerson elevator failed to start in 1997, and on # 736 would not close the doors in 2002. The # 735 alarm bell did not work in 2011. In December 2024 the lobby intercom and emergency phone did not work.
Five-year safety tests were requested in 2001, 2006, 2012 and 2013. The 2011 letter says required tests were not done in 2010, the 2013 letter says they were not done in 2012, and in 2024 required tests were not logged. This does not show every test went undone.
The April 2014 City report says the elevators were being modernized and would be inspected when the work was done. Our files do not include a sign-off for that work. The 2015 conveyance permit on file is for a new car interior in # 734.
The December 16, 2024 inspection listed water in the pit, the chains, the governor rope, test logs, the intercom and the emergency phone, with 90 days to finish: about March 16, 2025. Our files do not include a completion notice or what the City did after the deadline.
| Year | Inspected | What the City asked for |
|---|---|---|
| 1997 | August 5, 1997 | Elevator # 735: replace the governor cables (excessive crown and valley breaks). Elevator # 734: remove debris and liquids from the pit, correct the leaks and keep the pit dry. Fire service keys missing from the key box. Emerson elevator: Phase II fire service failed to start. |
| 1998 | October 4, 1998 | Elevator # 735: replace the governor cables, again. Pit debris. Fire service keys still not in the key box. |
| 2001 | January 4, 2001 | 31 corrections, including five-year safety tests and missing fire service keys. On car top wiring for # 734 the inspector wrote: "This has been a continuous repeat item every year." |
| 2002 | January 10, 2002 | Pit debris in # 735 and # 736. Phase II fire service on # 736 not working: "Cannot close doors." |
| 2003 | February 10, 2003 | Elevator # 734: remove liquids from the pit, correct the leaks and keep the pit dry. Fire service keys still missing. |
| 2006 | March 2, 2006 | Elevator # 734: shorten the governor rope. All elevators: perform a five-year safety test. |
| 2010 | April 6, 2010 | Elevator # 735: hoistway key missing from the key box; repair the leak in the machine room ceiling. |
| 2011 | April 14, 2011 | Pit debris in all elevators. Required tests "not done in 2010." Elevator # 735 alarm bell not working and pull box key missing from the key box. The letter says: "Many of these corrections are repeated from inspection reports of previous years." |
| 2012 | April 18, 2012 | Pit debris in all elevators. Five-year safety test of all elevators. Keys missing. The letter again says the corrections are repeated from previous years. |
| 2013 | April 2, 2013 | Pit debris and liquids. Required tests "not done in 2012." Three more fire service keys needed. Five-year safety test of # 734. |
| 2014 | April 29, 2014 | The City report says: "Elevators being modernized, will inspect at completion." |
| 2015 | May 6, 2015 | Pit debris in # 735 and # 736. |
| 2024 | December 16, 2024 | Result: Passed with Conditions. Lobby intercom and emergency phone not working. Required tests not logged. Shorten the governor rope. Shorten the compensation chains: "dragging on pit channel and wearing through steel." The pit has "8 to 10 inches of water and is rusting out all pit equipment." 90 days to complete. |
These letters list corrections the City asked for. An item missing from a later letter does not by itself show it was fixed, and an item that repeats does not by itself show it was never fixed in between. The building manager wrote to the City in June 2001 that corrections had been completed.
From the 113 matched addresses
Each address below has several rescue calls over a span of years, complaints that mention an elevator, and at least one elevator or lift not certified on the City's January 31, 2026 lists.
142 rescue calls · 1 elevator complaint
Rescue calls: February 2020 to June 2025. Complaint mentioning an elevator: November 2024. January 31, 2026 lists: 0 certified, 2 not certified.
An August 3, 2026 City notice says certificates were not issued for either elevator, after SDCI accepted a safety test on one of them on June 29, 2026.
To check: Why certificates were not issued after the accepted test.
52 rescue calls · 11 elevator complaints
Rescue calls: March 2021 to August 2025. Complaints mentioning an elevator: February 2019 to August 2023. January 31, 2026 lists: 1 certified, 3 not certified.
Read the Addison on 4th case study for this building.
To check: Complaint text, service history for each elevator and lift, and correction dates.
51 rescue calls · 3 elevator complaints
Rescue calls: April 2021 to June 2025. Complaints mentioning an elevator: January 2019 to February 2025. January 31, 2026 lists: 1 certified, 2 not certified.
One of the uncertified devices is an accessibility lift.
To check: Which device each rescue involved. The rescue log does not name a device.
50 rescue calls · 2 elevator complaints
Rescue calls: March 2022 to January 2026. Complaints mentioning an elevator: February 2025 to April 2025. January 31, 2026 lists: 1 certified, 3 not certified.
To check: Whether the repeated rescues involved the same elevator.
21 rescue calls · 19 elevator complaints
Rescue calls: August 2022 to December 2025. Complaints mentioning an elevator: August 2019 to January 2025. January 31, 2026 lists: 1 certified, 1 not certified.
To check: A timeline from each complaint to the City inspection that followed it.
10 rescue calls · 12 elevator complaints
Rescue calls: March 2022 to February 2025. Complaints mentioning an elevator: January 2023 to October 2025. January 31, 2026 lists: 0 certified, 2 not certified.
To check: Whether the complaints describe the same problem.
5 rescue calls · 11 elevator complaints
Rescue calls: August 2020 to August 2024. Complaints mentioning an elevator: April 2015 to March 2025. January 31, 2026 lists: 0 certified, 2 not certified.
To check: The full complaint text, to see whether it names the same problem.
What this list does not show: the same building does not mean the same elevator, repeated calls do not show an elevator stayed broken, and a certificate list label is a dated record status, not a safety finding.
| Address | Dist. | Rescue calls | Last rescue | Elevator complaints | Certified units | Uncertified units | Uncertified equipment records |
|---|
The 113 matched addresses only
| District | Addresses | Rescue calls | Elevator complaints | No certified unit |
|---|---|---|---|---|
| District 7 | 29 | 193 | 89 | 17 |
| District 3 | 21 | 70 | 53 | 16 |
| District 2 | 19 | 361 | 74 | 12 |
| District 4 | 14 | 92 | 17 | 11 |
| District 5 | 11 | 55 | 34 | 9 |
| District 1 | 11 | 37 | 36 | 8 |
| District 6 | 8 | 27 | 13 | 7 |
| All | 113 | 835 | 316 | 80 |